Scania DI9, DC9 with DEC2. Industrial engine. Instruction — part 2
Resetting functions with DIP switches in
control unit
There are 8 DIP switches in the control unit under the
round black rubber cover.
These switches should be in the ON position for
normal operation in accordance with the driving
program. For single speed engines, it may also be
normal for DIP switches 6, 7 and 8 to be in the OFF
position.
Shutdown at threshold values for low oil pressure and
high coolant temperature can be selected by setting
DIP switch 4 to OFF.
With DIP switch 4 in position ON, Power- indication
is obtained for these threshold values. Engine power
output reduction (LOP) can then be selected to prevent
damage to the engine. Changes to the program may be
made by authorised personnel only.
Note:
The engine should only be used in an
emergency when the Power- indication
comes on.
Reading fault codes
Note:
If the engine has stopped or lost power but
the main indicator lamp is out and neither
POWER- nor SHUTDOWN are on, the fault
is outside the control unit's detection area.
Probable causes: fuel starvation, temporary
overload, mechanical fault.
- Activate the lamp test/fault code switch. In
Scania's electrical equipment the main indicator
lamp is located in this switch in the main supply
box.
- All LEDs will then come on for 2 seconds to
indicate that they are intact and in working order.
This also applies to the main indicator lamp in the
main supply box and on the instrument panel
.
Make a note of any LED that is defective.
- All LEDs will then go out for approximately
4 seconds.
- Following this, a fault code will be indicated on
one of the LEDs for 2 seconds. Note which LED
it is.
- The control unit will then automatically return to
operating mode.
- After having made a note of the fault code, reset
the lamp test/fault code switch and reset the
control unit by turning off its power supply
momentarily.
- The most probable cause of the fault can then be
found in the troubleshooting schedule on the next
page.
- When the fault or faults have been rectified the
engine can be restarted.
- If the control system still gives an indication on
the main indicator lamp, other faults may be
registered. The fault codes must then read again
as above since the system can only show one fault
code at a time.
- The fault or faults will be logged in a special
memory in the control unit where the operating
time concerned is recorded. Stored faults can be
accessed and erased by authorised service
personnel.
18
READING F
A
UL
T CODES
LED INDICA
TION WHEN THE LAMP
TES
T
/F
AUL
T
CODE SWITCH IS ACTIV
A
TED
CONTROL STA
TUS
SHUTDOWN
STAR
TING
RUNNING
TO
RQUE LIMIT
BOOST LIMIT
POWER -
POWER +
Pr
obabl
e cause
A
ction
<
D
E
C2 has de
tected an
intern
al fault in the control
unit.
Se
nd i
n the
control unit for repair as soon as
possible.
<
The e
ngine
te
mperature has
re
ached the
thres
hold level
or the
temperature sensor is inoperative.
Check the cooling
system. Check the
te
mperature sensor and cable routing.
<
Th
e en
gin
e ha
s reac
he
d the
o
ve
rrev
vin
g limit or th
e
engine
speed sensor is inoperative.
Che
ck the wiring and connector.
R
ene
w the
eng
ine
spe
ed se
ns
or.
<
Control rack position sensor
inoperative.
Ch
eck connectors and
ca
bl
es to governor.
<
The inta
ke a
ir tempe
rature
has
re
ached
the thre
shold
le
vel or
the charge air tempera
ture se
nsor is
inoperat
ive.
Che
ck the inta
ke
sys
te
m
. Check the te
mperature
senso
r an
d
cabl
e ro
uti
ng.
<
D
E
C2 detects no charge air pre
ssure.
The charge air pre
ssure sensor is inoperative.
Che
ck the charge
air pres
sure
ca
ble. Se
nd
in
the
control unit if
the connect
ion
is damaged.
<
Engine speed potentiometer
or the idling safety
switch
is inoperat
ive.
Che
ck the cable routing,
co
nne
ctors
a
nd cables.
<
The oil pressure has dropped
to the
threshold level or
the oil pressure monitor is inope
ra
tive.
Check oi
l level,
connector and cable.
Renew t
he
oil pressure monitor.
<
= LED is on
STARTING AND RUNNING
AT FIRST START
When the engine is started for the first time, the maintenance points listed
under "First start" in the maintenance schedule should be followed, see
page 27.
Since the points are important for satisfactory operation of the engine right
from the outset, they are also listed below.
1. Checking the oil level (see page 29).
6. Checking the coolant level (see page 33).
The coolant should contain anti-corrosive to protect the cooling system
from corrosion.
If there is a danger of freezing:
- Only anti-freeze glycol should be used in the coolant as protection
against corrosion. We recommend only nitrite-free anti-freeze glycol
with the following supplier designations:
BASF G48 or BASF D542
- The concentration of glycol should be 30 - 60% by volume depending
on the ambient temperature. 30% glycol by volume provides anti-freeze
protection down to -16°C. See page 33.
- Never top up with only water or only glycol. Fluid losses must always
be replaced with pre-mixed coolant having the same glycol
concentration as that in the engine. If the glycol content drops, both
anti-freeze protection and protection against corrosion are impaired.
Note:
A glycol concentration below 30% by volume will not provide
sufficient protection against corrosion. Glycol concentrations
higher than 60% do not improve anti-freeze protection and have
a negative effect on engine cooling capacity.
Coolant composition:
If there is a danger of freezing:
minimum
30% glycol by volume
maximum
60% glycol by volume
If there is no danger of freezing:
7-12% by volume
Scania Corrosion Inhibitor
(no glycol)
The recommended glycols
should not be mixed with
glycol containing nitrite-based
corrosion inhibitor.
Ethylene glycol and
corrosion inhibitor
are toxic if ingested.
Avoid contact with the skin.
20
If there is no danger of freezing:
- Only Scania Corrosion Inhibitor should be used in the coolant as
protection against corrosion. The correct concentration of anti-corrosive
is 7-12% by volume and this must never drop below 7% by volume. The
inhibitor in Scania Corrosion Inhibitor is free of nitrite.
- First filling: Fill up the system with water + 10% by volume Scania
Corrosion Inhibitor. Use drinking water with a pH of 6 - 9.
- Never top up with only water or only anti-corrosive! Fluid losses must
always be replaced with blended coolant:
water + 10% Scania Corrosion Inhibitor by volume.
Coolant filter (not standard equipment)
Only coolant filter without inhibitor may be used. The use of coolant filters
increases the life of the coolant and reduces the risk of deposition corrosion.
12. Checking the fuel level (see page 40).
15. Checking the electrolyte level in batteries (see page 42).
16. Checking the state of charge in batteries (see page 42).
18. Checking the coolant level monitor (see page 43).
19. Checking the temperature monitor (see page 44).
20. Checking the oil pressure monitor (see page 45).
21. Checking transmission tension (see page 46).
Ethylene glycol and corrosion
inhibitor are
toxic if ingested.
Avoid contact with the skin.
Immobilise the starting device
when working on the engine.
If the engine starts out of
control, there is a
SERIOUS RISK
OF INJURY.
Overdosing with Scania
Corrosion Inhibitor and mixing
with glycol can cause sludge to
be formed.
If a coolant filter has been fitted
it must not contain inhibitor.
CHECKS BEFORE RUNNING
Before running, "Daily maintenance" as described in the maintenance
schedule should be carried out, see page 27.
STARTING THE ENGINE
If the fuel tank has been run dry or if the engine has not been used for a long
time, bleed the fuel system (see page 40).
Out of consideration for our common environment, your new Scania engine
has been designed to use a smaller amount of fuel when starting. Using
unnecessarily large amounts of fuel when starting the engine always results in
the discharge of unburnt fuel.
- Open the fuel cock, if fitted.
- Declutch the engine (not engines with fixed clutch, e.g. generator sets).
- Engines with battery master switch: Switch on the power by means of
the battery master switch.
- DEC2: If the main indicator lamp comes on or flashes when the power is
turned on, this indicates the presence of a fault in the control system or
engine which must be found and rectified before the engine is started.
See page 16.
- Start the engine by means of the starter button or starter key.
Starting at low temperatures
Local environmental requirements must be complied with. Starting aids,
engine heaters and/or flame start devices should be used to avoid starting
problems and white smoke.
To limit white smoke, the engine should be run at low speed and under
moderate load. Avoid running it longer than necessary at idling speed.
Start the engine only in a well
ventilated area.
If it is run in a enclosed space,
there should be an effective
device to draw off exhaust gases
and crankcase gases.
Never use starting spray or
similar to help you start the
engine.
An explosion may occur in the
intake manifold with a risk of
personal injury.
22
At temperatures below 0°C:
Note:
Only use starting aids recommended by Scania.
- The starter motor may only be used for 30 seconds at a time. After that
time it must rest for 2 minutes.
If the engine has flame start:
- Operating flame start without timer relay: Press the control button,
which also acts as a pre-glow button (maximum 20 seconds). The glow
plug continues to glow as long as this button is depressed after the
engine has started. Maximum time is 5 minutes.
- Operating flame start with timer relay: Press the pre-glow button
(maximum 20 seconds). Release it when the engine starts. The timer
relay keeps the glow plug glowing for 5 minutes. If a shorter glow time
is required, press the release button. The key must be set to the
0 position if the start attempt fails.
Note:
If the engine is equipped with an INTERLOCK switch, this
switch should be depressed and held down until the oil pressure
has reached a sufficiently high level.
- Generator sets should be operated under load immediately after starting
to avoid the risk of white smoke. This applies in particular to engines
that have been installed without aids for heating or applying a basic
load.
- Warm up the engine with a moderate load. A light load on a cold engine
gives better combustion and faster heating than warming up with no
load.
The starter motor may only be
connected for a maximum of
30 seconds.
There is risk of overheating.
Allow the engine to rest for
2 minutes between each
attempt to start it.
DRIVING
Check instruments and warning lamps at regular intervals.
Rotation speed
The Scania tachometer is divided into sectors of different colours, as follows:
Coolant temperature
Normal coolant temperature when the engine is running should be 70 - 90°C.
DEC2: If the temperature is high, 98°C or higher, it is possible to instruct the
control system to reduce the engine power (Power -) in order to lower the
temperature. See the DEC section on page 17.
If the temperature continues to rise, the engine will be stopped automatically
(Shutdown) at 103°C. See the DEC section on page 17.
Excessively high coolant temperature can damage the engine.
If run for extended periods under an extremely light load, the engine may
have difficulty in maintaining normal operating temperature. However, the
temperature will rise to a normal level again when the load on the engine is
increased.
0 - 500 rpm
red area:
prohibited engine speed,
passed when stopping and
starting.
500 - 700 rpm
yellow area:
slow idle.
700 - 2200 rpm
green area:
normal operating speed.
The engine's operating
speed range is controlled by
the DEC2 control system.
2200 - 2600 rpm
yellow/green
striped:
unsuitable operating speed.
May occur when switching
off and during downhill
engine braking
2600 - 3000 rpm
red area:
prohibited engine speed
WARNING! When driving the vehicle on a steep downhill
slope, or in other installations where the engine can be
driven by the vehicle movement, DEC2 will set zero
fuel supply to protect against overrevving and will
switch off the engine. It must not be disengaged in this
position since this can cause important functions such
as the steering and brake system to fail when the
engine stops rotating.
!
Cooling systems with Scania
radiators and plastic expansion
tanks must not have excess
pressure in the system, i.e.
pressure caps must not be used
on expansion tanks.
24
Oil pressure
Max. oil pressure:
warm engine running at a speed above 800 rpm
6 bar
Normal oil pressure:
warm engine running at an operating speed of
3 - 6 bar
Min. oil pressure:
warm engine running at a speed of 800 rpm
0.7 bar
At speeds below 800 rpm the gauge may show low oil pressure although no
fault is present.
Oil pressure below 0.7 bar at speeds above 800 rpm will cause engine
damage. The engine must be stopped immediately.
DEC2: The engine is stopped automatically if this function is selected.
See the DEC section on page 17.
Charging indicator lamp
If the lamp comes on during operation:
- Check/adjust the alternator drive belts as described under the
maintenance point. See page 46.
- If the charging indicator lamp is still on, this could be due to an
alternator fault or a fault in the electrical system.
STOPPING THE ENGINE
1.
Run the engine without a load for a few minutes if it has been run
continuously with a heavy load.
2.
Stop the engine with the stop button. Keep the stop button depressed
until the engine is completely stationary.
3.
DEC2: Before switching off, check that the control system's main
indicator lamp is not on or flashing. See page 16 for troubleshooting.
4.
Engines with battery master switch: Switch on the power by means of
the battery master switch. (Does not apply to emergency generator sets).
5.
Set the control switch to "0". (Does not apply to emergency generator
sets).
High lubricating oil pressure
(above 6 bar) is normal when
starting a cold engine.
High lubricating oil pressure
(above 6 bar) is normal when
starting a cold engine.
There is danger of turbo
damage and post boiling if the
engine is stopped without
cooling.
The power must not be
switched off before the engine
has stopped.
Clutch
- See the manufacturer's instructions for handling and operating the
clutch.
WARNING! If the clutch output shaft is rotating (e.g. in multiple
engine installations where other engines are running), the
clutch can, under its own power, be drawn to the engaged
position.
THIS CAN CAUSE INJURY and engine damage. For this
reason, always secure the clutch in the disengaged position
if there is a risk of the output shaft starting to rotate.
CHECKS AFTER RUNNING
- Check that the power is cut from the battery master switch and that the
control switch is in the "0" position.
- Fill the fuel tank. Make sure that the filler cap and the area round the
filler opening are clean to avoid contamination of the fuel.
- If there is a risk of freezing, the cooling system must be drained if it
does not contain sufficient glycol, see page 33.
- At temperatures below 0°C: Prepare for the next start by connecting the
engine heater.
Topping up with coolant
should be carried out when
the engine is stopped after
the first start.
Immobilise the starting device
when working on the engine.
If the engine starts out of
control, there is a
SERIOUS RISK OF
INJURY
26
MAINTENANCE
The maintenance programme covers 24 points, divided into the following
main groups:
Lubricating oil system . . . . . . . . . . . . . . . . . page 28
Cooling system . . . . . . . . . . . . . . . . . . . . . . . page 32
Air cleaner . . . . . . . . . . . . . . . . . . . . . . . . . . page 38
Fuel system. . . . . . . . . . . . . . . . . . . . . . . . . . page 40
Electrical system, monitors, batteries, etc. . . page 42
Miscellaneous. . . . . . . . . . . . . . . . . . . . . . . . page 46
The maintenance points are divided into intervals as follows:
Daily maintenance
Maintenance before the first start
Maintenance after the first 400 hours of operation
Periodic maintenance every 200 hours of operation (carried out after 200,
400, 600, 800, etc. hours)
Periodic maintenance every 400 hours of operation (carried out after 400,
800, 1200, 1600, etc. hours)
Periodic maintenance every 1200 hours of operation (carried out after 1200,
2400, 3600, etc. hours)
Periodic maintenance every 2400 hours of operation (carried out after 2400,
4800, etc. hours)
Periodic maintenance every 4800 hours of operation (carried out after 4800,
9600, etc. hours)
Annual Maintenance
Maintenance every 5th year
ENGINES WITH FEW OPERATING
HOURS
Emergency generator sets and the like that are not used regularly should be
run on test and checked in accordance with the generator set manufacturer's
instructions.
Run the engine until it reaches operating temperature and then carry out the
maintenance points below:
1. Checking oil level.
5. Checking coolant level.
8. Checking low pressure indicator.
12. Checking fuel level.
15. Checking electrolyte level in batteries.
16. Checking state of charge in batteries.
17. Cleaning batteries.
22. Look for leakage, rectify as necessary
Immobilise the starting device
when working on the engine.
If the engine starts out of
control, there is a
SERIOUS RISK OF
INJURY
For engines with few operating
hours that do not receive
periodic maintenance according
to the maintenance schedule on
page 27, maintenance should be
carried out in accordance with
the schedule:
"Annually"
"Every 5th year"
27
MAINTENANCE SCHEDULE
1.
More often if required
2.
For engines with few operating hours, see page 26.
3.
Earlier if low pressure indicator shows red.
4.
If inhibitor has not been topped up for five years, the coolant should be changed.
Daily
First
time at
Interval
At least
Firs
t sta
rt
40
0 h
20
0 h
40
0 h
12
00
h
24
00
h
48
00
h
Annually
Every 5th year
LUBRICATING OIL SYSTEM, page 28
1. Checking oil level
2. Oil change
1
3. Cleaning oil cleaner
1
4. Renewing the oil filter
1
COOLING SYSTEM, page 32
5. Checking coolant level
6. Checking coolant
4
7. Cleaning cooling system
1
AIR CLEANER, page 38
8. Test reading low pressure indicator
9. Cleaning the coarse cleaner
1
10. Cleaning or changing filter element
3
11. Changing safety cartridge
12. Checking fuel level
13. Changing main filter
1
14. Checking injectors
ELECTRICAL SYSTEM, page 42
15. Checking electrolyte level in batteries
2
16. Checking state of charge in batteries
2
17. Cleaning batteries
2
18. Checking level monitor
19. Checking temperature monitor
20. Checking oil pressure monitor
MISCELLANEOUS, page 46
21. Checking drive belt
22. Look for leakage, rectify as necessary
23. Checking/adjusting valve clearances
24. Changing (or cleaning) valve for closed crankcase
ventilation
28
LUBRICATING OIL SYSTEM
OIL GRADE
The engine oil must at least meet the requirements for one of the following
oil classifications:
- ACEA E3, E4 or E5
- The Total Base Number (TBN) should be minimum 12-13
(ASTM 2896).
- Check with your oil supplier that the oil meets these requirements.
- The specified oil change intervals are applicable provided that the fuel
sulphur content does not exceed 0.3% by weight. If the sulphur content
is greater than 0.3% but no more than 1.0%, the oil change interval must
be halved (200 h).
- Viscosities are shown in the figure below.
- When ambient temperatures are extremely low: Consult your nearest
Scania representative to avoid starting difficulties.
Oil analysis
Some oil companies can offer analysis of the engine oil. Such analysis
measures the oil's TBN (Total Base Number), TAN (Total Acid Number),
fuel dilution, water content, viscosity and the quantity of wear particles and
soot in the oil.
The result of a series of analyses is used as the basis for establishing a
suitable oil change interval.
If the conditions are changed, a new oil analysis programme must be carried
out to establish the new change interval.
Additives must not be used.
The oil should be suitable for
all temperature variations until
the next oil change.
-40
-30
-20
-10
0
10
20
30
40 °C
SAE 10W-30
SAE 20W-30
SAE 30
SAE 40
SAE 50
SAE 5W-30
SAE 15W-40
29
1. Daily:
CHECKING OIL LEVEL
Note:
Before checking oil level: Allow the engine to remain stationary
for at least 1 minute.
- The correct level is between the marks on the dipstick. Top up when the
level is at the lower mark.
- Correct type, see "Oil grade" on page 28.
Checking oil level during operation
On some engines the oil level can be checked during operation.
- Remove the oil filler cap to release the pressure in the crankcase.
- Check the level on the dipstick. Correct oil level: 10 mm below the Min.
or Max. mark.
2. Every 400 hours:
OIL CHANGE
Note:
If the engine is used for especially demanding operations,
particularly in a dusty environment or if the deposits in the
centrifugal cleaner are thicker than 20 mm: change the oil at
more frequent intervals.
- Unscrew the plug and drain the oil when the engine is hot.
- In certain engines the oil is pumped out by means of a bilge pump.
- Clean the magnet on the plug.
- Refit the plug.
- Fill up with oil.
- Check the level on the dipstick.
Max. 27 dm
3
Min. 20 dm
3
Max. 20 dm
3
Min. 16 dm
3
1 dm
3
= 1 litre
Maximum angles of inclination during operation
Maximum permissible angles during operation vary, depending on the type of
oil sump, see illustration.
Note:
Specified angle may only occur intermittently.
WARNING
The oil may be hot.
Wear protective gloves and
goggles
Max.
Min.
Use a container to avoid
spillage when changing the oil.
Dispose of used oil through an
authorised waste disposal
contractor.
30
3. Every 400 hours:
CLEANING THE OIL CLEANER
(at same time as an oil change)
- Unscrew the nut and remove the cover.
- Lift out the rotor and loosen the nut on the rotor bowl three turns.
- If the nut is jammed:
Clamp the nut, absolutely not the rotor, in a vice and turn the rotor three
turns by hand or with a screwdriver.
- Tap the nut lightly with your hand or a plastic hammer, to detach the
rotor bowl from the bottom plate.
- Unscrew the nut and remove the rotor bowl.
- Prize carefully to detach the strainer from the bottom plate.
- Scrape off the deposits from the inside of the rotor bowl. If there are no
deposits, this indicates that the cleaner is not working properly.
- If the deposits are thicker than 20 mm: clean more often.
Open the cap carefully. The
oil may be hot.
31
- Wash all parts in diesel oil.
- Fit the O-ring in the rotor bowl. Make sure it is not damaged.
Change if necessary.
- Assemble the rotor.
- Tighten the rotor nut firmly by hand
- Refit the rotor.
- Make sure that it spins easily.
- Check that the O-ring in the bowl is undamaged.
A hardened or damaged O-ring must be changed.
- Screw the bowl down hard by hand
If the nut is tightened with a tool, the rotor shaft, nut or bowl may be
damaged.
Functional inspection
The rotor rotates very fast and should continue to rotate when the engine has
stopped.
- Stop the engine when it is warm.
- Listen for a whirring sound from the rotor or feel whether the cleaner
housing is vibrating.
The rotor normally continues spinning for 30 - 60 seconds after the engine
has stopped.
If it does not: dismantle it and inspect the component parts.
32
4. Every 400 hours:
CHANGING THE OIL FILTER
(at same time as an oil change)
- Remove the old filter.
- Oil the rubber gasket and fit a new genuine Scania filter.
- Tighten the filter by hand.
Never use tools for this. The filter could sustain damage, obstructing
circulation.
- Start the engine and check for leaks.
Important!
If the deposits in the centrifugal cleaner are more than 20 mm
thick, the oil filter has to be replaced more often. The same is
true for cleaning the centrifugal filter and changing the oil.
COOLING SYSTEM
5. Daily:
CHECKING COOLANT LEVEL
- Open the expansion tank filler cap and check the coolant level.
- Correct level: (Scania plastic expansion tank)
- Cold engine: The coolant should be level with the bottom of the filler
neck.
- Hot engine: The coolant should be about 25 mm above the lower
edge of the filler hole.
- Other types of expansion tank according to the instructions of the fitter.
- Top up the coolant as necessary, see point 6.
Note:
When filling large amounts of coolant:
Never pour cold coolant into a hot engine.
This could crack the cylinder block and cylinder head.
Always top up with ready mixed
coolant.
Open the cap carefully.
Water and steam may
spray out.
Use a container to avoid spillage
when changing the filter.
Dispose of used filters through
an authorised waste disposal
contractor.
Нет комментариевНе стесняйтесь поделиться с нами вашим ценным мнением.
Текст