Nissan Titan A60. Manual — part 641
INSUFFICIENT COOLING
HAC-247
< SYMPTOM DIAGNOSIS >
[MANUAL A/C (TYPE 2)]
C
D
E
F
G
H
J
K
L
M
A
B
HAC
N
O
P
Performance Chart
INFOID:0000000006164847
TEST CONDITION
Testing must be performed as follows:
*1
VTL-12, "Removal and Installation"
*2
HAC-211, "Front Blower Motor Com-
ponent Function Check"
*3
HA-33, "Removal and Installation for
Compressor Clutch"
*4
*5
HA-32, "Removal and Installation for
Compressor"
AWIIA1000GB
HAC-248
< SYMPTOM DIAGNOSIS >
[MANUAL A/C (TYPE 2)]
INSUFFICIENT COOLING
TEST READING
Recirculation-to-discharge Air Temperature Table
Ambient Air Temperature-to-operating Pressure Table
Trouble Diagnoses for Abnormal Pressure
INFOID:0000000006164848
Whenever system
′s high and/or low side pressure is abnormal, diagnose using a manifold gauge. The marker
above the gauge scale in the following tables indicates the standard (usual) pressure range. Since the stan-
Vehicle location
Indoors or in the shade (in a well-ventilated place)
Doors
Closed
Door window
Open
Hood
Open
TEMP.
Max. COLD
Mode control dial
(Ventilation) set
Recirculation (REC) switch
(Recirculation) set
Blower speed
Max. speed set
Engine speed
Idle speed
Operate the air conditioning system for 10 minutes before taking measurements.
Inside air (Recirculating air) at blower assembly inlet
Discharge air temperature at center ventilator
°C (°F)
Relative humidity
%
Air temperature
°C (°F)
50 - 60
20 (68)
9.9 - 13.9 (50 - 57)
25 (77)
14.6 - 18.6 (58 - 65)
30 (86)
16.8 - 21.8 (62 - 71)
35 (95)
21.1 - 27.1 (70 - 81)
40 (104)
25.3 - 31.5 (78 - 89)
60 - 70
20 (68)
11.4 - 15.2 (53 - 59)
25 (77)
15.5 - 20.0 (60 - 68)
30 (86)
19.9 - 25.0 (68 - 77)
35 (95)
24.5 - 29.6 (76 - 85)
40 (104)
28.7 - 34.9 (84 - 95)
Ambient air
High-pressure (Discharge side)
kPa (kg/cm
2
, psi)
Low-pressure (Suction side)
kPa (kg/cm
2
, psi)
Relative humidity
%
Air temperature
°C (°F)
50 - 70
20 (68)
1020 - 1250
(10.4 - 12.7, 147.9 - 181.3)
160 - 190
(1.63 - 1.94, 23.2 - 27.6)
25 (77)
1236 - 1510
(12.6 - 15.4, 179.2 - 219)
206 - 245
(2.1 - 2.5, 29.9 - 35.6)
30 (86)
1569 - 1,922
(16.0 - 19.6, 227.6 - 278.8)
265 - 324
(2.7 - 3.3, 38.4 - 46.9)
35 (95)
1,697 - 2079
(17.3 - 21.2, 246.1 - 301.5)
304 - 363
(3.1 - 3.7, 44.1 - 52.6)
40 (104)
1971 - 2403
(20.1 - 24.5, 285.9 - 348.5)
373 - 451
(3.8 - 4.6, 54.0 - 65.4)
INSUFFICIENT COOLING
HAC-249
< SYMPTOM DIAGNOSIS >
[MANUAL A/C (TYPE 2)]
C
D
E
F
G
H
J
K
L
M
A
B
HAC
N
O
P
dard (usual) pressure, however, differs from vehicle to vehicle, refer to above table (Ambient air temperature-
to-operating pressure table).
Both High- and Low-pressure Sides are Too High
High-pressure Side is Too High and Low-pressure Side is Too Low
High-pressure Side is Too Low and Low-pressure Side is Too High
Gauge indication
Refrigerant cycle
Probable cause
Corrective action
Both high- and low-pressure sides
are too high.
Pressure is reduced soon af-
ter water is splashed on con-
denser.
Excessive refrigerant charge in
refrigeration cycle
Reduce refrigerant until speci-
fied pressure is obtained.
Air suction by cooling fan is in-
sufficient.
Insufficient condenser cooling
performance
↓
1.
Condenser fins are
clogged.
2.
Improper fan rotation of
cooling fan
• Clean condenser.
• Check and repair cooling fan
if necessary.
• Low-pressure pipe is not
cold.
• When compressor is
stopped high-pressure val-
ue quickly drops by approx-
imately 196 kPa (2 kg/cm
2
,
28 psi). It then decreases
gradually thereafter.
Poor heat exchange in con-
denser
(After compressor operation
stops, high-pressure decreas-
es too slowly.)
↓
Air in refrigeration cycle
Evacuate and recharge system.
Engine tends to overheat.
Engine cooling systems mal-
function.
Check and repair engine cool-
ing system.
• An area of the low-pressure
pipe is colder than areas
near the evaporator outlet.
• Plates are sometimes cov-
ered with frost.
• Excessive liquid refrigerant
on low-pressure side
• Excessive refrigerant dis-
charge flow
• Expansion valve is open a lit-
tle compared with the speci-
fication.
↓
Improper expansion valve ad-
justment
Replace expansion valve.
AC359A
Gauge indication
Refrigerant cycle
Probable cause
Corrective action
High-pressure side is too high and
low-pressure side is too low.
Upper side of condenser and
high-pressure side are hot,
however, liquid tank is not so
hot.
High-pressure tube or parts lo-
cated between compressor
and condenser are clogged or
crushed.
• Check and repair or replace
malfunctioning parts.
• Check oil for contamination.
AC360A
HAC-250
< SYMPTOM DIAGNOSIS >
[MANUAL A/C (TYPE 2)]
INSUFFICIENT COOLING
Both High- and Low-pressure Sides are Too Low
Low-pressure Side Sometimes Becomes Negative
Gauge indication
Refrigerant cycle
Probable cause
Corrective action
High-pressure side is too low and
low-pressure side is too high.
High- and low-pressure sides
become equal soon after com-
pressor operation stops.
Compressor pressure opera-
tion is improper.
↓
Damaged inside compressor
packings.
Replace compressor.
No temperature difference be-
tween high- and low-pressure
sides.
Compressor pressure opera-
tion is improper.
↓
Damaged inside compressor
packings.
Replace compressor.
AC356A
Gauge indication
Refrigerant cycle
Probable cause
Corrective action
Both high- and low-pressure sides
are too low.
• There is a big temperature
difference between liquid
tank outlet and inlet. Outlet
temperature is extremely
low.
• Liquid tank inlet and expan-
sion valve are frosted.
Liquid tank inside is slightly
clogged.
• Replace liquid tank.
• Check oil for contamination.
• Temperature of expansion
valve inlet is extremely low
as compared with areas
near liquid tank.
• Expansion valve inlet may
be frosted.
• Temperature difference oc-
curs somewhere in high-
pressure side.
High-pressure pipe located be-
tween liquid tank and expan-
sion valve is clogged.
• Check and repair malfunc-
tioning parts.
• Check oil for contamination.
Expansion valve and liquid
tank are warm or only cool
when touched.
Low refrigerant charge.
↓
Leaking fittings or compo-
nents.
Check refrigerant system for
leaks. Refer to
.
There is a big temperature dif-
ference between expansion
valve inlet and outlet while the
valve itself is frosted.
Expansion valve closes a little
compared with the specifica-
tion.
↓
1.
Improper expansion
valve adjustment.
2.
Malfunctioning expansion
valve.
3.
Outlet and inlet may be
clogged.
• Remove foreign particles by
using compressed air.
• Check oil for contamination.
An area of the low-pressure
pipe is colder than areas near
the evaporator outlet.
Low-pressure pipe is clogged
or crushed.
• Check and repair malfunc-
tioning parts.
• Check oil for contamination.
Air flow volume is too low.
Evaporator is frozen.
• Check intake sensor circuit.
Refer to
• Repair evaporator fins.
• Replace evaporator.
• Refer to
Blower Motor Component
Function Check"
AC353A
Нет комментариевНе стесняйтесь поделиться с нами вашим ценным мнением.
Текст