Toyota Tundra. Manual — part 2432
Fig. 147: Checking Refrigerant Pressure
Courtesy of TOYOTA MOTOR SALES, U.S.A., INC.
2. The A/C system periodically changes between normal and improper function due to moisture
in the refrigerant system.
Fig. 148: Checking Refrigerant Pressure - Moisture In Refrigerant System
Courtesy of TOYOTA MOTOR SALES, U.S.A., INC.
SYMPTOM DIAGNOSIS CHART
3. The A/C system does not function effectively due to insufficient cooling.
Symptoms
Probable Cause
Diagnosis
Corrective Actions
During operation,
pressure on low
pressure side
cycles between
normal and
vacuum
Moisture in refrigeration
system freezes at
expansion valve orifice,
causing temporary stop
of cycle. However,
when melted, normal
state is restored.
Drier is overly
saturated
Moisture in
refrigeration system
freezes at expansion
valve orifice and
blocks refrigerant
circulation
1. Replace cooler
drier
2. Remove
moisture from
cycle by
repeatedly
evacuating air
3. Supply
appropriate
volume of new
refrigerant
2009 Toyota Tundra
2009 HVAC Air Conditioning - Tundra
Fig. 149: Checking Refrigerant Pressure - Insufficient Cooling
Courtesy of TOYOTA MOTOR SALES, U.S.A., INC.
SYMPTOM DIAGNOSIS CHART
4. The A/C system does not function effectively due to poor circulation of the refrigerant.
Fig. 150: Checking Refrigerant Pressure - Poor Circulation Of Refrigerant
Courtesy of TOYOTA MOTOR SALES, U.S.A., INC.
SYMPTOM DIAGNOSIS CHART
Symptoms
Probable
Cause
Diagnosis
Corrective Actions
Pressure low on
both low and
high pressure
sides
Cooling
performance
insufficient
Gas leakage
from
refrigeration
system
Insufficient
refrigerant
Refrigerant
leakage
1. Check for gas leakage and
repair if necessary
2. Supply appropriate
volume of new refrigerant
3. If indicated pressure value
close to 0 when connected
to gauge, create vacuum
after inspecting and
repairing the location of
leakage
Symptoms
Probable Cause
Diagnosis
Corrective
Actions
Pressure low on both low
and high pressure sides
Frost exists on piping from
condenser to A/C unit
Refrigerant flow obstructed
by dirt in condenser
Condenser
clogged
Replace
condenser
2009 Toyota Tundra
2009 HVAC Air Conditioning - Tundra
5. The A/C system does not function or functions intermittently because the refrigerant does not
circulate.
Fig. 151: Checking Refrigerant Pressure - Refrigerant Does Not Circulate
Courtesy of TOYOTA MOTOR SALES, U.S.A., INC.
SYMPTOM DIAGNOSIS CHART
6. The A/C system does not function effectively due to overcharged refrigerant or insufficient
cooling of the condenser.
Fig. 152: Checking Refrigerant Pressure - Overcharged Refrigerant Or Insufficient
Symptoms
Probable Cause
Diagnosis
Corrective Actions
Vacuum indicated on
low pressure side, and
extremely low
pressure indicated on
high pressure side
Frost or condensation
seen on piping on both
sides of condenser or
expansion valve
Refrigerant flow
obstructed by
moisture or dirt in
refrigeration
system
Refrigerant flow
obstructed by gas
leakage from
expansion valve
Refrigerant
does not
circulate
1. Check expansion
valve refrigerant
2. Clean expansion
valve by
blowing air
3. Replace
condenser
4. Evacuate air and
charge
appropriate
volume of new
refrigerant
5. For gas leakage
from expansion
valve, replace
expansion valve
2009 Toyota Tundra
2009 HVAC Air Conditioning - Tundra
Cooling Of Condenser
Courtesy of TOYOTA MOTOR SALES, U.S.A., INC.
SYMPTOM DIAGNOSIS CHART
7. The A/C system does not function due to air in the refrigeration system.
Fig. 153: Checking Refrigerant Pressure - Air In Refrigeration System
Courtesy of TOYOTA MOTOR SALES, U.S.A., INC.
HINT:
These gauge indications occur when the refrigeration system opens and the refrigerant is
charged without vacuum purging
SYMPTOM DIAGNOSIS CHART
Symptoms
Probable Cause
Diagnosis
Corrective Actions
Pressure
extremely high
on both low and
high-pressure
sides
Excessive
refrigerant
Cooling
performance of
condenser
insufficient
Condenser is
dirty
Condenser fan
motor is
malfunctioning
Excessive
refrigerant
1. Clean condenser
2. Check condenser fan
motor operation
3. If 1 and 2 normal,
check the amount of
refrigerant and
supply appropriate
volume of
refrigerant
CAUTION: The low-pressure piping may be very hot and cause
serious burns.
Symptoms
Probable
Cause
Diagnosis
Corrective Actions
Pressure extremely
high on both low and
high-pressure sides
Low-pressure piping
Air in
refrigeration
system
Air in
refrigeration
system
Vacuum
purging
1. Check if
compressor oil is
dirty or
insufficient
2. Evacuate air and
2009 Toyota Tundra
2009 HVAC Air Conditioning - Tundra