Mitsubishi Montero (2004+). Manual — part 665
HEATER UNIT
TSB Revision
AUTOMATIC AIR CONDITIONING
55B-149
DISASSEMBLY AND REASSEMBLY
M1554009200083
ASSEMBLY SERVICE POINT
.
>>A<< HEATER WATER TEMPERATURE SENSOR/HEATER
WATER TEMPERATURE SENSOR CLIP INSTALLATION
Insert the heater water temperature sensor into the mounting
hole on the heater unit, and secure the sensor with the clip.
AC205222
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
N
N
N
AB
DISASSEMBLY STEPS
1.
FOOT DUCT A
2.
FOOT DUCT C
3.
AIR THERMO SENSOR CLIP
4.
AIR THERMO SENSOR
>>A<<
5.
HEATER WATER TEMPERATURE
SENSOR CLIP
>>A<<
6.
HEATER WATER TEMPERATURE
SENSOR
7.
MODE SELECTION DAMPER
CONTROL MOTOR
8.
AIR MIXING DAMPER CONTROL
MOTOR
9.
ASPIRATOR HOSE
10. HEATER BLOWER CONTROLLER
UNIT
11. REAR COOLER CONTROL UNIT
OR REAR A/C CONTROL UNIT
12. JOINT DUCT
13. AIR DUCT SUBASSEMBLY
14. HEATER CORE
15. FRONT PIPE ASSEMBLY
16. EXPANSION VALVE
17. PIPE
18. EVAPORATOR
19. CASE
DISASSEMBLY STEPS
HEATER BLOWER CONTROLLER UNIT
TSB Revision
AUTOMATIC AIR CONDITIONING
55B-150
HEATER BLOWER CONTROLLER UNIT
REMOVAL AND INSTALLATION
M1554009400010
INSPECTION
M1554009500017
BLOWER LINER CONTROLLER
When the connector is connected and the ignition switch is
turned ON, the voltage at terminal 2 should be as follows:
AC101450
BLOWER LINER
CONTROLLER
AB
BLOWER SWITCH POSITION
VOLTAGE AT TERMINAL
No. 2 V
LOW SPEED
4.0
MEDIUM SPEED
7.9
HIGH SPEED
13.7
ACX00825AC
DAMPER CONTROL MOTOR ASSEMBLY
TSB Revision
AUTOMATIC AIR CONDITIONING
55B-151
DAMPER CONTROL MOTOR ASSEMBLY
REMOVAL AND INSTALLATION
M1554001600032
INSPECTION
M1554001700051
.
AIR MIX DAMPER CONTROL MOTOR CHECK
CAUTION
Do not apply battery voltage when the damper is in the
MAX COOL or MAX HOT position.
Check the air mix damper control motor by the following proce-
dures.
ACX01447
1
2
REMOVAL STEPS
•
UNDER COVER (REFER TO
GROUP 52A, INSTRUMENT
PANEL
.)
1.
AIR MIX DAMPER MOTOR
2.
AIR OUTLET CHANGEOVER
DAMPER MOTOR
REMOVAL STEPS (Continued)
ACX01456
MAX HOT
POSITION
MAX COOL
POSITION
AB
DAMPER CONTROL MOTOR ASSEMBLY
TSB Revision
AUTOMATIC AIR CONDITIONING
55B-152
.
POTENTIOMETER CHECK
While checking the air mix damper control motor, measure the
resistances between terminals numbers 3 and 5 as well as
numbers 3 and 7. At this time, the resistances should change
gradually within the standard value.
Standard value: 1.2
− 4.8 k
.
MODE SELECTION DAMPER CONTROL MOTOR CHECK
CAUTION
Do not apply battery voltage when the damper is in the
FACE or DEF position.
Check the mode selection damper control motor by the follow-
ing procedures.
.
POTENTIOMETER CHECK
While checking the mode selection damper control motor, mea-
sure the resistances between terminal numbers 3 and 5 as well
as terminal numbers 3 and 7. At this time, the resistances
should change gradually within the standard value.
Standard value: 0.96
− 5.76 kΩ
LEVER
POSITION
BATTERY
CONNECTION
LEVER
OPERATION
At the MAX
COOL position
• Connect terminal 1
to the positive
battery terminal
• Connect terminal 2
to the negative
battery terminal
The lever moves
from the MAX
COOL position to
the outside position
At the MAX
HOT position
• Connect terminal 2
to the positive
battery terminal
• Connect terminal 1
to the negative
battery terminal
The lever moves
from the MAX HOT
position to the
inside position
LEVER
POSITION
BATTERY
CONNECTION
LEVER
OPERATION
At the DEF
position
• Connect terminal 1
to the positive
battery terminal
• Connect terminal 2
to the negative
battery terminal
The lever moves
from the DEF
position to the
outside position
At the FACE
position
• Connect terminal 2
to the positive
battery terminal
• Connect terminal 1
to the negative
battery terminal
The lever moves
from the FACE
position to the
inside position
ACX01457
FACE POSITION
DEF POSITION
AB